State of Ohio Fire Alarm Test Practice Questions and Verified Answers, 100% Score Guarantee Pass (Latest 2025)
Smoke detectors for door release services shall be: - Correct
Answers ✅photoelectric type ionization other approved type The number of supervisory devices permitted to be connected to a single initiating device circuit shall not exceed _____ - Correct Answers ✅Fifteen True or False The fire marshal must approve a presignal system - Correct Answers ✅True Power limited fire alarm cable shall have a voltage rating of _____ Volts? - Correct Answers ✅30V What type of fire alarm system transmits alarms to a public fire service? - Correct Answers ✅municipal fire alarm system 1 / 4
State of Ohio Fire Alarm Test Practice Questions and Verified Answers, 100% Score Guarantee Pass (Latest 2025) Wall mounted audible notification appliances shall have their tops above finished floor at heights of not less than __ inches and below the finished ceilings at distances not to exceed inches - Correct Answers ✅90,6 When manual fire alarm boxes are used, the distance between boxes will not be in excess of - Correct Answers ✅200ft A signaling method characterized by simultaneous or sequential transmission or both, and reception of multiple signals in a transmission channel including means for positively identifying each signal is - Correct Answers ✅multiplexing All - Correct Answers ✅Air duct detectors shall be installed in such a way as to obtain a representative sample of the air stream. This installation shall be
permitted to be achieved by any of the following methods:
rigid mounting within the duct 2 / 4
State of Ohio Fire Alarm Test Practice Questions and Verified Answers, 100% Score Guarantee Pass (Latest 2025) rigid mounting to the wall of the duct with the sensing element protruding into the duct outside the duct with rigidly mounted sampling tubesprotruding into the duct through the duct with projected light beam All Smoke detectors shall be spaced within ___ feet of the peak measured horizontally - Correct Answers ✅3 The minimum decibel level for fire alarm signal is ___ ? - Correct Answers ✅75db Visible notification appliances shall be installed within _ feet of the end of the corridor with a separation of no greater than _____ feet - Correct Answers ✅15,100 True or False 3 / 4
State of Ohio Fire Alarm Test Practice Questions and Verified Answers, 100% Score Guarantee Pass (Latest 2025) It is permissible for the fire alarm system to share a circuit with the exit lights - Correct Answers ✅False NFPA standard 72E suggests using what method to test heat detectors - Correct Answers ✅hair dryer Manual fire alarm boxes shall be ___ in color. - Correct Answers ✅red Actuation of alarm notification appliances or emergency voice communications, fire alarm safety functions, and annunciation at the protected premises shall occur within activation of the initiating device - Correct Answers ✅10 True or False In one or two family dwelling units a smoke detector shall be placed on each level, including the basement - Correct Answers ✅True
- / 4