- | P a g e
RETA Industrial Refrigeration Book 3 Exam Newest 2025 Complete 200 Questions And Correct Answers (Verified Answers) |Already Graded A+
A spring loaded self-closing valve could be part of an oil sampling manifold if? (pg. 3-4)
- A spiral tube is downstream of the ball valve
- The fittings upstream of the valve can handle the torque applied to
- The MP calls for it
- The ball section is vented - ANSWER-B) The fittings upstream of the
hold the valve open
valve can handle the torque applied to hold the valve open
Which statement is NOT true about lowering the discharge pressure on a condenser by running the evaporative condenser at full load? (pg. 4-6)
- You can lower the head pressure so low that it will cause other
- Lowering the head pressure while keeping the suction pressure
system problems
constant will reduce the amount of horsepower required by the compressor saving energy 1 / 4
- | P a g e
- Lowering the head pressure will save wear and tear on the
- Lowering the head pressure will always make the system more
compressor
efficient and cost less to run - ANSWER-D) Lowering the head pressure will always make the system more efficient and cost less to run
Which of these statements are true about passivation in an evaporative condenser? (pg. 4-18)
- During passivation you should keep the pH as low as possible,
- You should keep the pH between 7 and 8 during passivation
- You are only concerned about passivating the tubes in an evaporator
- After a condenser has been properly passivated, you never have to
preferably between 1 and 2
condenser
worry about white rust again - ANSWER-B) You should keep the pH between 7 and 8 during passivation
Which is NOT a cause of scale formation on the evaporative condenser tubes? (pg. 4-18)
- Improper water treatment
- Plugged spray or partially plugged spray nozzles
- Improper passivation of a new condenser
- Not enough bleed water going down the drain - ANSWER-C)
- / 4
Improper passivation of a new condenser
- | P a g e
The purpose of the eliminators in an evaporative condenser is? (pg. 4- 21)
- To eliminate the formation of scale on the tubes of the condenser
- To prevent or eliminate the possibility of the water pumps cavitating
- To prevent the formation of white rust
- To prevent water droplets from being blown from the condenser -
due to air entrainment
ANSWER-D) To prevent water droplets from being blown from the condenser
The primary functional difference between a cooling tower and an evaporative condenser is where the? (pg. 4-7)
- Refrigerant condenses
- Where the unit must be shut down
- Water distribution system is located
- Filtration stream will be collected - ANSWER-A) Refrigerant
condenses
What are the two types of condenser designs for air flow? (pg. 4-23)
- Forced draft and induced draft
- Forced draft and up draft
- Up draft and down draft
- Centrifugal and axial - ANSWER-A) Forced draft and induced draft
- / 4
- | P a g e
Compressor efficiency increases when condensers? (pg. 4-6)
- Use water on days with very high wet bulb
- Lower discharge pressure
- Are bottled up with liquid
- Let the discharge pressure rise - ANSWER-B) Lower discharge
pressure
One of the most common causes of poor condenser performance is? (pg.
4-19,21)
- Loose belt on the fans
- Too much fans horsepower used
- Scale on the condenser tube bundle
- Too much water in the sump - ANSWER-C) Scale on the condenser
tube bundle
If you are having problems with the capacity of your condenser, you should check? (pg. 4-22)
- Wet bulb temperature of the inlet air compared to the surrounding
- The fit of the eliminators
- Motor horsepower
- For white rust buildup in the condenser - ANSWER-A) Wet bulb
- / 4
area
temperature of the inlet air compared to the surrounding area