TFM03 Fire Extinguisher Safety and Compliance – Texas Fire Department – Practice Test Questions and Verified Answers (Latest Update, Graded A)

Question : Operating devices shall operate at

CORRECT ANSWER : 32F to 120F

Question : Manual actuators shall not have a force more than

CORRECT ANSWER : 40lbs

Question : Manual actuators shall not have a movement of

more than

CORRECT ANSWER : 14 inches

Question : Instructions with pictographs and lettering shall be

atleast

CORRECT ANSWER: 1/4 inches

Question : Pipe and fittings shall be made of

CORRECT ANSWER : Non combustible materials

Question : galvanized pipe and fittings

CORRECT ANSWER : Shall not be used

Question : During assembly examine pipe

CORRECT ANSWER : Internally to detect and remove

contaminants

Question : Readily acces means for manual actuators

CORRECT ANSWER : Shall be located in a path of egress

Question : Manual actuators shall be installed

CORRECT ANSWER : No more than 48in and no less than

42in

Question : Fusible links shall be located

CORRECT ANSWER : At above each cooking appliance

Question : Fusible links shall be

CORRECT ANSWER : 12 in in front of said item

Question : A test shall be used on pipe using

CORRECT ANSWER : Nitrogen or dry air not exceeding

normal operating pressure

Question : Piping shall not

CORRECT ANSWER : Be hydrostatic tested

Question : Owners inspection

CORRECT ANSWER : Monthly

Question : Owners inspection records shall be retained

CORRECT ANSWER: Semi-annualy

Question : Wet chemical fire extinguisher service at

CORRECT ANSWER : Every 6 months

Question : Wet chemical fire extinguishing system service at

CORRECT ANSWER : 6 months

Question : wet chemical fire extinguishing system with fire

damage,corrosion,welds etc

CORRECT ANSWER : Shall be hydrostatic tested

Question : Maintenance reports shall be kept

CORRECT ANSWER : For a year

Question : Fixed temperature sensing elements otger than

fusible metal alloys shall be replaced

CORRECT ANSW ER: Every 12 months

Question : Fixed temperature sensing elements of fusible

metal alloys shall be replaced

CORRECT ANSWER : Semi-annualy

Question : Wet chemical extinguisher hydrostatic test

Download Document

Buy This Document

$30.00 One-time purchase
Buy Now
  • Full access to this document
  • Download anytime
  • No expiration

Document Information

Category: Study Guides
Added: Aug 18, 2025
Description:

TFM03 Fire Extinguisher Safety and Compliance – Texas Fire Department – Practice Test Questions and Verified Answers (Latest Update, Graded A) Question : Operating devices shall operate at CORR...

Get this document $30.00