Kentucky UST Certification Test Prep

Study Guides Aug 18, 2025
Loading...

Loading document viewer...

Page 0 of 0

Document Text

Kentucky UST Certification Test Prep | 160 Questions and Answers 100% Correct

Question : 1. when tanks arrive at the job site, how should

they be unloaded?

Correct answer: lifted off with a cable attached to the tank

lifting lugs

Question : As an alternative lifting method, should a cable or

chain be wrapped around the tank?

Correct answer: No, Never!

Question : When you are lifting a tank, using the lifting lugs,

which of these procedures should be followed?

Correct answer: attach a triangle cable through the lugs with

no more than a 30 degree angle from the center line.

Question : After you unload a new tank on a clean level

surface at the job site what else should you do prior to inspection and pre-testing?

Correct answer: Chock the tank to prevent it from Rolling

Question : which of the following items should be physically

checked for damage or imperfections at the job site?

Correct answer: Piping (steel and fiberglass)

Fittings, Vents, Fillboxes, anodes, ECT..The tanks themselves

(ALL OF THE ABOVE)!

Question : STI-P3 tanks are delivered with shipping plugs in

tank openings. What should be done to these plugs prior to testing?

Correct answer: remove the plugs and replace them with a

standard threaded plug that is properly doped

Question : should dielectric bushings be installed in all

openings of an STI-P3 tank?

Correct answer: yes on all openings

Question : what is the maximum air pressure to which a steel

tank should be subjected in a pre-installation test?

Correct answer: 5 pounds

Question : for fiberglass reinforced plastic (FRP) tanks up to

12 feet in diameter what is an acceptable air pressure to which the tanks may be subjected in a pre-installation test?

Correct answer: 3 pounds

Question : for FRP tanks over 12 feet in diameter what is the

maximum air pressure to which the tanks should be subjected in a pre-installation test?

Correct answer: 3 pounds

Question : when you are conducting an air test on a tank the

type of gauge that should be used is?

Correct answer: a pressure gauge with a maximum limit of 10

to 15 PSIG

Question : the proper procedure for conducting a pre-

installation air test of a steel tank is to?

Correct answer: apply 3 to 5 pounds of pressure and soap all

surfaces and weld seams visible through the coating while inspecting for bubbles.

Question : what is the proper procedure for conducting a pre-

installation air test of an FRP tank Under 12 feet in diameter is to....

Correct answer: apply 3 pounds of air pressure and soap all

surfaces while inspecting for any sign of a leak either audible or visible in the form of bubbles on the surface

Question : a double-walled steel tank build in accordance with

UL standard 58 is?

Correct answer: requires air testing of the interstitial space

prior to installation

Question : the proper procedure for conducting a pre-

installation air test of a double-walled tank is to?

Download Document

Buy This Document

$30.00 One-time purchase
Buy Now
  • Full access to this document
  • Download anytime
  • No expiration

Document Information

Category: Study Guides
Added: Aug 18, 2025
Description:

Kentucky UST Certification Test Prep | 160 Questions and Answers 100% Correct Question : 1. when tanks arrive at the job site, how should they be unloaded? Correct answer: lifted off with a cable a...

Get this document $30.00