ELECTRICAL LEVEL 3 M ODULE 1 LOAD

CALCULATIONS AND BRA NCH FEEDER

CIRCUITS QUESTIONS AND ANSWERS

WITH SOLUTIONS

Question :What is the demand load for one household range

with a nameplate rating of 11.75kW, 240V, 1Ø?

Correct answer:8kW

Question :What is the lighting load on a 120V circuit for six

100W incandescent lights and four fluorescent fixtures with a ballast rating of 1.5A, all operating continuously for 8 hours per day? 13.75A

Correct answer:13.75A

13.75A

Question :What is the load center distance for a 208V, four-

wire, three-phase branch circuit with fixed noncontinuous loads from the source of 60A at 45', 40A at 60', 30A at 75', and 25A at 100'

Correct answer:63.55'

63.55'

Question :What is the load center length for a branch circuit

consisting of noncontinuous loads of 125A at 80', 75A at 110', and 50A at 100'?

Correct answer:93'

93'

Question :What is the load center length for a branch circuit

with noncontinuous loads of 20A at 60' and 50A at 125'?

Correct answer:106.43'

106.43'

Question :What is the load for 55' of show window using the

linear foot method?

Correct answer:13,750VA

13,750VA

Question :What is the motor full-load current for a motor

with a nameplate rating of 50hp, 460V, 3Ø?

Correct answer:65A

65A

Question :What is the required circuit ampacity for a

noncontinuous, three-phase load of 6kW at 208V?

Correct answer:16.65A

16.65A

Question :What is the total ampacity for a 120V branch

circuit consisting of four duplex receptacles rated noncontinuous duty and six duplex receptacles rated continuous duty?

Correct answer:17.25A

17.25A

Question :What is the total load required by the NEC® for

two appliance branch circuits plus a laundry branch circuit?

Correct answer:4,500VA

4,500VA

Question :What size copper conductor would be required for

a 240V, 1Ø circuit supplying a noncontinuous load of 27.5A at a distance of 145', and a maximum voltage drop of 3%?

Correct answer:No. 10

No. 10

Question :When connected to 15A or 20A multi-outlet

general-purpose branch circuits, which of the following shall not exceed 50% of the branch circuit ampere rating?

Correct answer:Fastened-in-place utilization equipment

Fastened-in-place utilization equipment

Question: According to the NEC®, the ampacity of branch

circuit conductors must be derated when there are more than how many current-carrying conductors in a raceway?

Correct answer: 3

Question: Air conditioning overcurrent protective devices

can never exceed what percentage of the motor-rated load current or the branch circuit selection current (whichever is greater)?

Correct answer: 225%

Question: When must conductors be derated when installed

in conduit?

Correct answer: On or above rooftops

Question: At what percentage of the maximum current rating

of the overcurrent device are continuous loads calculated?

Correct answer: 80%

Question: For a given load and length, what should the

branch circuit voltage drop not exceed?

Correct answer: 3%

Question: For resistance welders, what should the rating for

the overcurrent protection device not exceed as a percentage of the primary current rating of the welder?

Download Document

Buy This Document

$30.00 One-time purchase
Buy Now
  • Full access to this document
  • Download anytime
  • No expiration

Document Information

Category: Study Guides
Added: Aug 18, 2025
Description:

ELECTRICAL LEVEL 3 M ODULE 1 LOAD CALCULATIONS AND BRA NCH FEEDER CIRCUITS QUESTIONS AND ANSWERS WITH SOLUTIONS Question :What is the demand load for one household range with a nameplate rating of ...

Get this document $30.00