CSFSM S-56 Exam Latest Update 2024 Questions and Verified Correct Answers Guaranteed A+
- per 1,000 sq. ft - CORRECT ANSWER: fire extinguisher required with operational
coke salamander temporary heat. Max travel distance is 75 ft.
1 standard size Acet. Bottle - CORRECT ANSWER: 420 SCF
1 standard size oxy bottle - CORRECT ANSWER: 307 SCF
2-A rating - CORRECT ANSWER: at least 1 fire extinguisher next to each small
ammunition storage area
2,500,000 cartridges - CORRECT ANSWER: This is the limit in which you can store
small arms ammunition or smokeless propellants.
2A 20: BC - CORRECT ANSWER: minimum fire extinguisher rating on the jobsite
3-A 40-B:C - CORRECT ANSWER: Minimum fire extinguisher rating for hot work roofing operations.
3,500 SCF - CORRECT ANSWER: Indoor storage of flammable gas shall not be more
than this amount per control area. Two 3,500 SCF cages shall be separated by 50 feet.
15 cubic yards - CORRECT ANSWER: This amount of combustible material must be
removed daily before end of day.
15,000 SCF - CORRECT ANSWER: The max storage quantity for flammable gases in
any building or structure
25 gallons of flammable liquids - CORRECT ANSWER: Max limit for storing flammable liquids outside approved storage.
40-B:C - CORRECT ANSWER: rating for wheeled fire extinguisher. Kept within 30 ft from flammable liquid storage cage.
60 minutes or more - CORRECT ANSWER: When hot work has stopped for more than
60 minutes torch valve and gas supply needs to be closed-circuit.
75 ft & 1,500 sq. ft - CORRECT ANSWER: maximum travel distance for fire
extinguishers or area of room
400 SCF - CORRECT ANSWER: FDNY permits required when storing, handling,
using flammable gases
- / 2
660 Gallons - CORRECT ANSWER: What is the max capacity for temporary
aboveground flammable liquid tanks?
A-49 - CORRECT ANSWER: Supervision of aerosals
Aerosol storage requirements - CORRECT ANSWER: Using / storing over 100 lbs of
level 2 or 3 products. Chain link fence used to enclose cage, min. #9 gage steel w/ 2'' diamond mesh. All combustibles kept min. 8' away.
After hours fire guard - CORRECT ANSWER: Required when jobsite exceeds 10,000
sq. ft fronting one street or 20,000 when fronting two streets or whenever it exceeds 75 ft in height.
ANSI A13.1 - CORRECT ANSWER: Standpipes painted red or ID by lettered legend.
Citywide permit - CORRECT ANSWER: normally issued when hot work operations are
anticipated to be completed in 30 days or less
Class 1,II, III liquids - CORRECT ANSWER: Containers exceeding 5.3 gallons at 20F degrees less than their flash points shall not be dispensed by gravity.
Class IA, IB, IC - CORRECT ANSWER: Flammable liquids based on flashpoint /
boiling point
Class II, IIIA, IIIB - CORRECT ANSWER: Combustible liquids based on flashpoint
Combo standpipe - CORRECT ANSWER: Valve handles marked yellow
Combustible Liquid Definition - CORRECT ANSWER: Any liquid whose flashpoint
exceeds 100 F. Degrees
combustible materials during hot work - CORRECT ANSWER: all of these types of
materials shall be more than 35 ft away from the operation or shielded / protected.
Crane Aerial Fueling P-54 regs. - CORRECT ANSWER: COF for P-54 must be
present at all times during fueling. Portable tank should be grounded to crane.
E-21 - CORRECT ANSWER: Using powder activated tools
Electrical interconnection - CORRECT ANSWER: Metallic floor plates which
containers stand while filling or where the fill stem is bonded to the container during filling by a bond wire.
F-01 - CORRECT ANSWER: COF for impairment