TFM02 - FEL B Exam Questions and Answers (Verified Answers) Latest Update
Question : The hydrostatic test interval for a dry chemical
extinguisher with a stainless steel shell is every __ years
CORRECT ANSWER : 5
Question : The hydrostatic test interval for a stored-pressure
water, water mist, loaded stream, and/or antifreeze is __ years
CORRECT ANSWER : 5
Question : The hydrostatic test interval for a Wetting agent
extinguisher is __ years.
CORRECT ANSWER : 5
Question : The Hydrostatic test interval for a AFFF (aqueous
film-forming foam) extinguisher is __ years.
CORRECT ANSWER : 5
Question : The Hydrostatic test interval for a FFFP (film-
forming fluoroprotein foam) extinguisher is __ years.
CORRECT ANSWER : 5
Question : The hydrostatic test interval for a Carbon Dioxide
extinguisher is __ years.
CORRECT ANSWER : 5
Question : The hydrostatic test interval for a Wet Chemical
extinguisher is __ years.
CORRECT ANSWER : 5
Question : The hydrostatic test interval for a Dry chemical,
stored-pressure, with mild steel shells, brazed brass shells, or aluminum shells is __ years.
CORRECT ANSWER : 12
Question : The hydrostatic test interval for a Dry chemical,
cartridge- or cylinder- operated, with mild steel shells is __ years.
CORRECT ANSWER : 12
Question : The hydrostatic test interval for a Halogenated
Agent extinguisher is __ years.
CORRECT ANSWER : 12
Question : The hydrostatic test interval for a Dry powder,
stored-pressure, cartridge- or cylinder- operated, with mild steel shells extinguisher is __ years.
CORRECT ANSWER : 12
Question : The maintenance internal examination for a stored-
pressure loaded stream and antifreeze is __ years.
CORRECT ANSWER : 1
Question : The maintenance internal examination for a Pump
tank water and pump tank, calcium chloride based extinguisher is __ years.
CORRECT ANSWER : 1
Question : The maintenance internal examination for a dry
chemical, cartridge- and cylinder- operated, with mild steel shells extinguisher is __ years.
CORRECT ANSWER : 1
Question : The maintenance internal examination for a Dry
powder, cartridge- and cylinder- operated, with mild steel shells extinguisher is __ years.
CORRECT ANSWER : 1
Question : The maintenance internal examination for a
Wetting agent extinguisher is __ years
CORRECT ANSWER : 1
Question : The maintenance internal examination for a
Stored-pressure water extinguisher is __ years.
CORRECT ANSWER : 5
Question : The maintenance internal examination for a AFFF
- aqueous film-forming foam) extinguisher is __ years.