California UST Service Technician part 1 Exam 100% Complete Test Pass With Your First Attempt A written statement indicating SIR results must be submitted to the ____every____ - Correct Answer Local agency , 12 months
According to EO VR 101 E maintance records are required to include? - Correct Answer Name and designated UST operator .
According to EO VR 201 A What could cause a nozzle shut off mechanism or malfunction? - Correct Answer Depended filter seal damage
According to EO VR 2010 after installing a new spout assembly in the Healy 900 nozzle the following test must be conducted ? - Correct Answer Nozzle dispensing shut off test
According to Healy EO VR 201 A a vapor recovery record are to be maintained by? - Correct Answer Gasoline dispensing facility operator (GDF)
According to PEI RP 300 a combustible gas can be used to ? - Correct Answer Detect vapor leaks in a vapor recovery system.
According to PEI RP 300 as built drawing or pictures of the underground pipping and other components shall be ? - Correct Answer Maintained as long as UST is in service
According to PEI RP 300 the following method of documenting piping location is NOT to ? - Correct Answer Sketch a diagram on the inside cover of vapor recovery equipment manual
According to PEI RP 300. A written scope of work for vapor recovery installation should include? - Correct Answer Construction plCorrect Answer
According to the health and safety code the owner of a new tank must conduct a one time ELD test if the tank is located within 1000 ft of a public drinking water well. This test must accomplished by ? - Correct Answer January 1, 2005
According to title 23; the following piping components if installed after July 1 1987 must have secondary containment - Correct Answer Pressured product piping
According to VR 201 A Breakaway reconnection must be ? - Correct Answer Logged in GDF log
An approved method for non visual monitoring for existing UST systems. - Correct Answer Statistical Inventory Reconciliation (SIR)
- / 2
An unauthorized release which does not escape secondary containment, requires only recordation on the Operators Manual Report provided. - Correct Answer It did not cause deterioration of secondary containment.It did not increase the hazard of fire.It was cleaned up within eight hours addicti it was cleaned up within eight hours detection.
ATG must be capable for detecting a release of ? - Correct Answer .2 gallons per hour
ATG should be programmed to test the tank ? - Correct Answer At least monthly
Automatic line leak detectors installed on underground piping with secondary containment shall be capable of tetecting a leak of ? - Correct Answer 3 gallons per hour at 10 psi
Cathodic protection systems must be tested within ____Months of installation and every ____months thereafter. - Correct Answer 6, 36
Considered "pipe" on tanks installed after July 1 2003 - Correct Answer Pressured product piping and below ground vapor recovery
Enhanced the detections results must be submitted to ___ within ___days - Correct Answer The local agency and State water resources control Board.60
how many feet within a public drinking well require an enhanced leak detection test - Correct Answer 1000 feet
ICC cert must be renewed every? - Correct Answer 24 months
If An authorize release meets reporting requirements of title 23 section 2652 the report must be filed within the? - Correct Answer Local agency
If an unauthorized product release meets the requirements for reporting to the local agency, verbal notification must be made within ____hours, followed by a written notification within ____days. - Correct Answer 24, 5
If equipped with an over fill alarm, it must be located? - Correct Answer So it can be seen or heard from the delivery location.
If installed, the following requires independent 3rd party certification to prove compliance with established regulations. - Correct Answer Automatic Tank Gauge Liquid Product Detectors SIR
- / 2